34 point I/O module.
Inputs: (16) Universal inputs.
Outputs: (10) Form A relay outputs; (8) 0-10VDC analog outputs.
Note:
– Maximum (8) IO-R-34 can be connected to the EC-BOS-8 over RS-485.
– IO-R-34 is powered by 24VAC/DC.
– IO-R-34 can power (4) IO-R-16.
EC-BOS-8 includes two isolated RS485 ports, two 10/100MB Ethernet ports, USB Backup & Restore and Wi-Fi connectivity. Worldwide WiFi setting for enabling WiFi on EC-BOS-8 units installed anywhere in the world except the US.
EC-BOS-8 core software. Includes all available drivers. Supports up to 500 devices or 25000 points. Runs on EC-Net 4.1 or higher and EC-Net AX (minimum v3.8.111). Note: This license expires annually and its renewal is covered by the EC-Net Support Fee.